• QUESTIONS? GIVE US A CALL! 1 (877) 293-0784

Navigate to the Spycor Environmental homepage

Envirco Hospi-Gard® IsoClean® HEPA Filtration System, Hospital Isolation for SARS COVID-19
Envirco Hospi-Gard® IsoClean® HEPA Filtration System, Hospital Isolation for SARS COVID-19 - Image 1 of 0
Envirco Hospi-Gard® IsoClean® HEPA Filtration System, Hospital Isolation for SARS COVID-19 - Image 2 of 0
Envirco Hospi-Gard® IsoClean® HEPA Filtration System, Hospital Isolation for SARS COVID-19 - Video 3 of 1
Envirco Hospi-Gard® IsoClean® HEPA Filtration System, Hospital Isolation for SARS COVID-19 - Image 1 of 0
Envirco Hospi-Gard® IsoClean® HEPA Filtration System, Hospital Isolation for SARS COVID-19 - Image 2 of 0
Envirco Hospi-Gard® IsoClean® HEPA Filtration System, Hospital Isolation for SARS COVID-19 - Video 3 of 1
Envirco Hospi-Gard® IsoClean® HEPA Filtration System, Hospital Isolation for SARS COVID-19 - Image 1 of 0
Envirco Hospi-Gard® IsoClean® HEPA Filtration System, Hospital Isolation for SARS COVID-19 - Image 2 of 0
Envirco Hospi-Gard® IsoClean® HEPA Filtration System, Hospital Isolation for SARS COVID-19 - Video 3 of 1

Envirco Hospi-Gard® IsoClean® HEPA Filtration System with UV-C

Koch
0 Reviews
$0.00
*1 Year Manufacturer Warranty
Product Code: T10850-005
Usually Ships in 3 to 5 Business Days
The Envirco Hospi-Gard® IsoClean® is a portable, self-contained high efficiency particulate air (HEPA) filtration system designed to easily and economically create a negative pressure isolation room/environment that will meet OSHA andCDC TB guidelines. UV-C Sanitizer

The IsoClean® can be used as a positive pressure clean air recirculating system in clinics,waiting rooms, hospital emergency rooms and other confined areas or as a partial or complete exhausting system to create a negative pressure isolation room for possible use with patients known or suspected of having TB, SARS or other infectious diseases.

As a recirculating unit, the IsoClean®’s powerful motor/blower can deliver from 560 CFM (951 m3/hr) up to 800 CFM (1359 m3/hr) to provide a large number of room air changes per hour to minimize the spread of airborne diseases to patients and health care workers.

As a negative pressure unit, the air passing through the HEPA filter is cleansed of 99.99% of particles as small as 0.3 micron and may be exhausted directly to the exterior through a window, or through a wall simply by connecting flexible ducting to the 6 in. (152 mm) collar located on the top of the IsoClean®.

The Hospi-Gard® IsoClean® filter contains 220 square feet (20.4 square meters) of media to extend its usable lifetime before filter loading occurs, resulting in decreased cost and fewer filter changes.

Low Cost Isolation Room
An easy and economical solution for creating a negative pressure, isolation room. Simply roll the IsoClean® into a standard room, connect flexible ducting tothe 6 in. (152 mm) collar on the top of the unit for partial exhaust or to theoptional 8 in. (204 mm) flanged collar for total exhaust and vent the purified air to the exterior through a window or wall.

Flexible Applications
The versatile IsoClean® can be used as a clean air recirculating unit, a negative pressure unit or as a split system to create both negative pressure and clean air recirculation by simultaneously exhausting some of the air out while recirculating the remainder back into the room.

Small and Portable
The IsoClean® can be rolled from one room to another and easily fits into areas with limited floor space.Quiet Operation52 dBA on low, 56 dBA on medium and 60dBA on high speed measured 30 in. (762mm) from face of the unit.

3-Speed Adjustable Airflow
The IsoClean® provides effective air filtration for a wide variety of room sizes with speeds ranging from 560 to 800CFM (951-1359 m3/hr).

Room Air Changes Per Hour
Provides up to 24 room air changes per hour(ACH)inatypical18x12x8ft(5.5 x 3.7 x 2.4 m) patient room or up to 12 ACH for rooms up to 3,900 cubic feet(100 cubic meters).

Low-High Clean Air Circulation Pattern
Room air, along with airborne contaminants, is drawn into the intake grille at the bottom while the purified air is discharged at a high velocity from the exhaust grille located at the top of the IsoClean® to generate a sweeping, low-to high air circulation pattern with adequate “reach” to optimize the clean breathingzone for patient and staff.

Simple Maintenance
Both HEPA filter and prefilter are easily accessible for replacement by authorized personnel.

Air Flow Calculator (link)

Hospital Applications:Other ApplicationsOptions:
  • Negative Pressure Rooms Emergency Rooms
  • Waiting Rooms
  • Sputum Induction
  • Aerosol Pentamidine Treatment Intensive Care Units
  • Bronchoscopy Rooms
  • Renal Dialysis Rooms
  • Clinics
  • Nursing Centers
  • Physician Offices
  • Homeless Shelters
  • Addiction Recovery Centers
  • Correctional Facilities
  • IsoClean with ULPA Filter Upgrade
  • Minihelic Pressure Gauge
  • Keylock ON/OFF Switch
  • Anti-Microbial Prefilter
  • Carbon Prefilter
  • 8 in. (203 mm) 100% Exhaust Collar
  • Room Pressure Monitor Annunciator
  • 220 V, 50/60 Hz Unit Available
  • UV-C Sanitizer Available

Construction
Welded steel filter plenum and blower housing with a corrosion resistant polyurethane enamel finish. Four 2” (51 mm) casters, two locking.

FilterAluminum
Framed HEPA type, with a minimum efficiency of 99.99% @ 0.3 micron, aerosol challenged. Airflow sensor indicates when the filter needs changing.

Prefilter

Disposable non-woven polyester media with frame -30% ASHRAE.

6 in. (152 mm) Exhaust Port

Located on top of the unit for use as a split system to create both negative pressure and cleanair recirculation.

Motor/Blower Assembly
Direct drive, continuous duty, 1/3 Hp, 0.25 kW, 3-speed motor with sealed-for-life bearings and inherent overload protection located on the “clean side” of the filter. Motor/blower assembly is mounted on vibration dampening rubber mounts and designed to provide rated airflow through a 50% increase in initial static pressure.

Electrical
Standard 5-15P, 115 V, single phase,rubber-covered cord with3-prong hospital grade, grounded plug (120V Model). Standard6-15P, 220 V, single phase, rubber-covered cord with 3-pronghospital grade, grounded plug (220V Model).


Description

120V with UV

220V with UV

120V

220V

Part No.

10850-005

10921-004

10850

10921

Dimension Inches (mm)

A

62.25 (1581)

B

19.75 (502)

15.75 (400)

C

23.66 (601)

D

12.86 (327)

8.86 (225)

UL Listed (E152685)

No

No

YesN

o

page2image3234902576

(m3/hr)

Low: 560 (951) ± 10%

Medium: 690 (1172) ± 10%

High: 800 (1359) ± 10%

Power Requirements

8 Amps @ 115V/ 60 Hz

4.0 Amps @ 208-230V/ 60 Hz

6.9 Amps @ 115 vac/ 60 Hz

3.5 Amps 208-230 vac/ 60 Hz

Unit Weight lbs. (kg.)

200 (91)

175 (79)

Shipping Weight lbs. (kg.)

285 (129)

250 (113)

Shipping Dimensions (mm)

A

71.5 (1816)

B

22.75 (578)

18.75 (476)

C

26.75 (680)

Reviews

Average Customer Review:
( 0 )